Valves
Product Categories
- Air Vent
- Compensators
- Delegated Design Services
- Energy-Saving Pump Connectors
- Fire Protection
- Fittings
- Flexible Couplings
- Flexible Metal Hose
- Metal Expansion Joints
- Metraflex Riser Package
- Metraloop®
- Pipe Guides and Anchors
- Rubber Expansion Joints
- Seismic BreakAway Hanger
- Strainers
- Valves
- VRF Expansion Joints
- Wall Penetration Seals
VFD Check Valve
- First Center Guided Silent Check Valve specifically designed for use with a VFD
- Product is more Hydrodynamic due to reshaping the disk
- Same face-to-face dimensions as traditional check valves
- Improves the Cv 38% operating at 6 FPS
- Available in sizes 2.5″ through 12″
- 150 lb. Class and 300 lb. Class
Submittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
CloseSubmittals
Close
Why is my check valve chattering?
The most common reason a check valve chatters is turbulence. Very often the turbulence is caused because the check valve is installed too close to the discharge of a pump or is just downstream of an elbow or some other turbulence causing device. Valve manufacturers, including Metraflex recommend 5-10 straight diameters of pipe directly upstream of the check valves. This allows any turbulence in the system to settle out prior to reaching the check valve. Turbulent flow will cause the disc to be loaded in a random way causing the disc to flutter and bounce.
There are two possible solutions if your check valve is chattering:
1. Move the check valve further downstream from any turbulence causing equipment.
2. Install a Vane Flex, a flex connector with built in straightening vanes, upstream of the check valve.